HYBRID INVERTER
6.0kw Single Phase
Integrated streamlined case designwith elegantappearance
IP66 system protection rating
Flexible setting of multiple workingmodes according to preferences
Seamless switching ofemergencymode to ensure that loads do not power down
EAHI series is an inverter charger that supports diversified energy management modes on solar/utility/generator charging, and utility/inverter power supply to the AC loads. To maximize solar energy utilization, users can choose energy sources according to actual needs and flexibly take the utility as a supplement. This solar inverter charger can raise the system's power supply guarantee rate, which is suitable for solar energy, utility/oil generator hybrid systems. It aims to provide users with high-quality, high-stability, and high-reliability electrical energy.
INVERTER MODEL |
EAHI-6000-SL-S |
PV input parameter |
Maximum input power |
8000W |
Maximum input voltage |
550Vdc |
Rated input voltage |
360Vdc |
Starting voltage |
100Vdc |
Minimum operating voltage |
150Vdc |
MPPT operating voltage |
100~540Vdc |
PV maximum input current |
16A/16A |
PV maximum short circuit current |
24A/24A |
Quantity of independent MPPT |
2 |
Number of input strings per MPPT |
1/1 |
Battery input parameter |
Battery type |
Lithium battery |
Battery voltage range |
42~58Vdc |
Maximum charging current |
100A |
Maximum discharge current |
120A |
Charging curve |
3 Stages/Equalization |
Lithium battery charging strategy |
BMS self-adaption |
AC input parameter (grid side) |
Grid type |
Single phase |
Input voltage range |
184~276Vac |
Input frequency range |
50±5Hz/60±5Hz |
Maximum input current |
40A |
AC output parameter (grid side) |
Rated output power |
6000W |
Maximum apparent output power |
6000VA |
Grid system mode |
1/N/PE |
Rated output voltage |
220Vac/230Vac |
Rated output frequency |
50Hz/60Hz |
Rated output current |
27.3A/26.1A |
Maximum output current |
27.3A |
Power factor |
>0.99 (0.8 lead~0.8 lag) |
Total current harmonics |
≤3% (rated power) |
AC output parameter (back-up side) |
Rated output power |
6000W |
Maximum apparent output power |
6000VA |
Grid system mode |
1/N/PE |
Rated output voltage |
230Vac (208/220/240Vac settable) |
Rated output frequency |
50Hz/60Hz |
Rated output current |
27.3A/26.1A |
Voltage harmonic |
≤3% (linear load) |
Switching time |
≤10ms |
Efficiency |
Maximum efficiency |
97.8% |
MPPT efficiency |
99.9% |
Protection |
Comprehensive |
Grid over-voltage protection, grid over-frequency protection, grid overload protection, over-temperature protection, anti-islanding protection, insulation resistance detection, residual current monitoring unit, output over-current protection, output short-circuit protection, surge protection |
Surge protection |
DC Type II/AC Type III |
Standard |
Safety regulation |
IEC/EN 62109-1/-2, AS62109 |
EMC |
EN 61000-6-1/-2/-3/-4 |
Grid-tied |
CEI 0-21, DIN VDE V 0124-100:2020, VDE-AR-N 4105:2018, AS4777.2, NRS097-2-1, EN 50549-1, G99/1-9:2022, ETSI EN303645+PSTI, C10/11:2021, XP C 15-712-3:2019, ELOT EN 50549-1:2019, PEA |
Other |
Topology |
High frequency isolation (to batteries) |
IP rating |
IP66 |
Operating temperature range |
-25~60ºC (derated at >45ºC) |
Cooling method |
Natural cooling |
Maximum altitude |
4000m |
Noise |
≤25dB |
Installation method |
Floor-mounted |
Dimensions (WxHxD)(mm) |
600×530×305 |
Weight (kg) |
36.4 |