Customization: | Available |
---|---|
Nature of Source Flow: | Active Inverter |
Certification: | CE |
Still deciding? Get samples of US$ 5345/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | HUS50kW | HUS 60kW | HUS80kW | HUS100kW | HUS120kW | HUS150kW | HUS160kW | |||||||
TECHNICAL | ||||||||||||||
BATTERY |
Nominal voltage | 48V/96V/192V/384Vdc | ||||||||||||
Charging current | 0-45A | |||||||||||||
Charging voltage | 55.2Vdc for 48Vdc (*2 for 96Vdc; * 4 for 192Vdc, *8 for 384Vdc) battery set | |||||||||||||
Battery high voltage alarm |
60Vdc for 48Vdc (*2 for 96Vdc; *4 for 19Vdc; *8 for 384Vdc) battery set | |||||||||||||
Battery low voltage alarm |
42Vdc for 48Vdc (*2 for 96Vdc; *4 for 19Vdc; *8 for 384Vdc) battery set | |||||||||||||
Battery type | Lead acid battery /gel/li batteries (optional) | |||||||||||||
INPUT |
Phase | 3L+N+PE | ||||||||||||
Voltage range | 380V/400Vac ± 1% | |||||||||||||
Frequency range | 45Hz~55Hz (50Hz) / 55Hz ~ 65Hz (60Hz) | |||||||||||||
Charging mode | 3 stages: constant current (MPPT), balanced charge, floating charge | |||||||||||||
OUTPUT |
Phase | 3L+N+PE | ||||||||||||
Voltage | 380V/400Vac ± 5% | |||||||||||||
Frequency | 50/60Hz ±1% (auto-adaptation) | |||||||||||||
Distortion | Linear load ≤ 3% | |||||||||||||
Efficiency | ≥ 85% | |||||||||||||
Switch time | ≤ 4ms | |||||||||||||
Surge power | 15kVA | 24kVA | 30kVA | 45kVA | 60kVA | 75kVA | 90kVA | |||||||
Waveform | Pure sine wave | |||||||||||||
Unbalanced load | Support | |||||||||||||
Protection | Overvoltage, undervoltage, overload, over temperature, surge, short circuit | |||||||||||||
Display | LCD + LED | |||||||||||||
Heat dissipation mode | Fan | |||||||||||||
Harmonic distortion | THD ≤3% (resistive load) | |||||||||||||
Communication protocol |
RS232/RS485/App/Wi-Fi | |||||||||||||
WORKING MODE |
Grid prior | Priority is given to power grid, and transfers to battery inverter when power grid is abnormal | ||||||||||||
Eco mode | The device automatically goes into sleep mode when the load is empty | |||||||||||||
PV prior | PV first, and when PV is not enough, battery and grid complement each other | |||||||||||||
ENVIRONMENTAL |
Humidity | 0% ~ 90% relative humidity (non-condensing) | ||||||||||||
Environmental temperature |
-10 ~ 50°C | |||||||||||||
Storage temperature | -15 ~ 60°C | |||||||||||||
PHYSICAL | Dimension (mm) | 785x640x1400 | 980x825x1560 | 1185x960x1750 | ||||||||||
Net weight (kg) | 365 | 390 | 550 | 650 | 670 | 750 | 810 |